Arc Flash Mitigation With Maintenance Mode

arc flash

Introduction To Maintenance Mode

The Arc Flash Mitigation with Maintenance Mode provides a method to reduce clearing time of arc flash energy. A circuit breaker equipped with Maintenance Mode can improve safety by providing a simple and reliable method to reduce fault clearing time. Maintenance Mode uses a separate analog trip circuit that provides faster interruption times than the standard (digital) “instantaneous” protection. Work locations downstream of a circuit breaker with a Maintenance Mode unit can have a significantly lower incident energy level.

Benefits of Molded Case Circuit Breaker with Maintenance Mode

  • Increased worker safety, when enabled, Maintenance Mode provides an accelerated instantaneous trip to reduce arc flash
  • The operator can pre-select from five levels of protection to facilitate the maximum arc-flash reduction while avoiding nuisance tripping during planned startup and maintenance operations without disturbing the normal operational trip unit settings.
  • Once the setting for Maintenance Mode has been properly chosen, Maintenance Mode is enabled by a simple lockable switch that can be incorporated into a lockout/tagout (LOTO) procedure.
  • The lockable switch is mounted on the front door, or remotely, up to 9.78 ft (3m) away from the breaker, eliminating the need to open the door to enable it (no special PPE required).
  • Maintenance Mode is designed to be used only during the time that a worker is exposed to the flash hazard. Maintenance Mode is not activated or armed continuously. This feature improves overcurrent coordination when compared to a permanently installed instantaneous trip element on the same circuit breaker
  • Reduction in incident energy levels may allow reduced levels of PPE to be used, offering an improvement to worker comfort and mobility.
  • When properly applied, the hazard risk category frequently can be lowered one or two categories, permitting less PPE.

How is Maintenance Mode used to reduce incident energy?

When Maintenance Mode is enabled and fault current is detected, the clearing time of the associated circuit breaker is reduced.

The table below shows how incident energy varies with fault duration times where the bolted fault level is 40 kA:

Incident energy
Incident energy calculated using IEEE 1584-2002 for 480V system @ working distance of 24 inches

How is the pickup setting of Maintenance Mode chosen?

The pickup settings must be chosen by a person who is qualified in power system analysis. The initial setup of each Maintenance Mode System will require power system analysis to determine the fault currents that flow through the circuit breaker associated with the Maintenance Mode unit. Maintenance Mode has five pickup settings that are based on multiples of the per unit secondary current monitored by the trip unit of its associated circuit breaker (2.5X, 4X, 6X, 8X or 10X rating plug).

The pickup setting is chosen using the following steps:

  1. Calculate the arcing fault current that could flow through the circuit breaker associated with the Maintenance Mode System. The table shows that arcing fault current is much lower than that of the bolted fault current. Formulas from IEEE STD 1584TM-2002 are used to calculate the arcing current.
  2. Determine the total transient load current that can flow to loads fed by the circuit breaker equipped with the Maintenance Mode System. These can include motor inrush and transformer inrush.

Choose a pickup setting for the Maintenance Mode System that is:

  • Below 75% of calculated arcing current.
  • Above the total transient load current.

Myths about Maintenance Mode System unit

Myth 1: All it does is turn the instantaneous setting down to a lower value.

FALSE: Unlike other products, the Maintenance Mode System involves a separate circuit that acts faster than the standard “instantaneous” protection.

The Maintenance Mode System is an analog circuit that provides faster interruption times versus the digital “instantaneous” protection (~20 ms faster).

Faster interruptions = less fault current let through = less arc flash energy

Myth 2: Nuisance trips occur because of noise.

FALSE: Noise does not affect protection as explained for activation methods that follow:

Local at the trip unit—The Maintenance Mode System circuit has passed all the tests that a normal trip unit needs to pass for noise immunity: RF, Surge, Burst. This is as robust as any normal molded case circuit breaker.

External switch—The trip unit circuit is in Off/Remote Enable mode. An external switch can then be mounted on the gear and wired to the breaker to enable or disable the mode. This has been tested up to 9.78 ft (3m) away from the switch to the breaker. It has passed all the “noise” tests at that maximum length. For added assurance, WEG recommends that the switch be mounted reasonably close to the breaker.

Relevant Contents

Related Posts

protection coordination
ETAP
Chief Editor

Protection and Coordination Analysis

This article demonstrates the high level step by step procedure to perform the protection and coordination analysis in ETAP software. Below are the steps: Select protective devices models from editor Once the single line diagram and data entry is complete

Read More »
directional protection
Protection
Chief Editor

Directional Overcurrent Protection

Application Directional Overcurrent Protection is useful for all network components in which the direction of flow of power is likely to change, notably in the instance of a short circuit between phases or of an earthing fault (single phase fault).

Read More »
Tur-Gov
Electrical Equipment
Chief Editor

Generator Turbine Governor Control

Introduction The generator turbine governor control regulates rotational speed in response to changing load conditions. The governor output signal manipulates the position of a steam inlet valve or nozzles which in turn regulates the steam flow to the turbine. Turbine-generator

Read More »
Digsilent Power Flow Analysis
DIgSILENT
Chief Editor

DIgSILENT Load Flow Analysis

This article shows the step by step process on how to run DIgSILENT Load Flow Analysis. This will help engineers to practice on how to run load flow analysis on DIgSILENT Power Factory Software. Sample Network Model You can setup

Read More »
short circuit
General
Chief Editor

X/R Ratio in Low-Voltage Short Circuit Studies

This article discusses about the importance of X/R ratio in low voltage short circuit studies. Introduction In some short circuit studies, the X/R ratio is ignored when comparing the short circuit rating of the equipment to the available fault current

Read More »
harmonic frequency scan
General
Chief Editor

Harmonic Analysis Methods

Harmonic analysis methods help engineers to calculate system harmonic levels resulting from harmonic sources on the system. This also requires a knowledge of the harmonic source characteristics and a representation of the system frequency response characteristics. Below sections cover the

Read More »

Author Information

Comments

Leave a Reply

Your email address will not be published. Required fields are marked *