Generator Turbine Governor Control

Tur-Gov

Introduction

The generator turbine governor control regulates rotational speed in response to changing load conditions. The governor output signal manipulates the position of a steam inlet valve or nozzles which in turn regulates the steam flow to the turbine.

Turbine Governor Control
Turbine Governor Control

Turbine-generator units operating in a power system contain stored kinetic energy due to their rotating masses. If the system load suddenly increases, stored kinetic energy is released to initially supply the load increase. Also, the electrical torque Te of each turbine-generating unit increases to supply the load increase, while the mechanical torque Tm of the turbine initially remains constant.

Generator Dynamics

From Newton’s second law, Jα = Tm – Te, the acceleration α is therefore negative. That is, each turbine-generator decelerates and the rotor speed drops as kinetic energy is released to supply the load increase. The electrical frequency of each generator, which is proportional to rotor speed for synchronous machines, also drops.

From this, we conclude that either rotor speed or generator frequency indicates a balance or imbalance of generator electrical torque Te and turbine mechanical torque Tm.

If speed or frequency is decreasing, then Te is greater than Tm (neglecting generator losses). Similarly, if speed or frequency is increasing, Te is less than Tm. Accordingly, generator frequency is an appropriate control signal for governing the mechanical output power of the turbine.

The steady-state frequency-power relation for turbine-governor control is:

steady-state frequency-power relation
Equation – (1)

where ∆f is the change in frequency, ∆Pm is the change in turbine mechanical power output, and ∆Pref is the change in a reference power setting. ‘R’ is called the regulation constant.

Below figure shows the family of curves for above equation, with ∆Pref as a parameter. Note that when ∆Pref is fixed, ∆Pm is directly proportional to the drop in frequency.

steady-state frequency-power relation

Above figure illustrates a steady-state frequency-power relation. When an electrical load change occurs, the turbine-generator rotor accelerates or decelerates, and frequency undergoes a transient disturbance. Under normal operating conditions, the rotor acceleration eventually becomes zero, and the frequency reaches a new steady-state, shown in the figure.

The regulation constant ‘R’ is the negative of the slope of the ∆f versus ∆Pm curves as per above figure. The units of R are Hz/MW when ∆f is in Hz and ∆Pm is in MW. When ∆f and ∆Pm are given in per-unit, however, R is also in per-unit.

Frequency-Power Relation of an Interconnected Power System

The steady-state frequency-power relation for one area of an interconnected power system can be determined by summing Equation – (1) for each turbine-generating unit in the area. Noting that ∆f is the same for each unit,

steady-state frequency-power relation for interconnected power system
Equation – (2)

where ∆Pm is the total change in turbine mechanical powers and ∆Pref is the total change in reference power settings within the area. We define the area frequency response characteristic β as:

area frequency response characteristics
Equation – (3)

Using Equation – (3) in Equation – (2),

area frequency response characteristics
Equation – (4)

Equation – (4) is the area steady-state frequency-power relation. The units of β are MW/Hz when ∆f is in Hz and ∆Pm is in MW. β can also be given in per-unit.

Turbine Governor Block Diagram

Turbine Governor Block Diagram
Turbine Governor Block Diagram

A standard value for the regulation constant is R = 0.05 per unit. When all turbine-generating units have the same per-unit value of R based on their own ratings, then each unit shares total power changes in proportion to its own rating.

Above figure shows a block diagram for a simple steam turbine governor commonly known as the TGOV1 model. The 1/(1 + sT1) models the time delays associated with the governor, where ‘s’ is again the Laplace operator and T1 is the time constant. The limits on the output of this block account for the fact that turbines have minimum and maximum outputs.

The second block diagram models the delays associated with the turbine; for non-reheat turbines T2 should be zero. Typical values are R = 0.05 p.u., T1 = 0.5 seconds, T3 = 0.5 for a non-reheat turbine or T2 = 2.5 and T3 = 7.5 seconds otherwise. Dt, is a turbine damping coefficient that is usually 0.02 or less (often zero).

Example

Example

Relevant Contents

Related Posts

Electrical Equipment
Chief Editor

Selection of NGR (Neutral Grounding Resistor)

Selection of NGR mainly depends on key factors such as the voltage rating, the time rating and the let-through-current rating. Voltage Rating An NGR must be rated for system line-to-neutral voltage—the voltage across the resistor when a single-phase bolted ground

Read More »
Transformer Inrush
PSCAD
Ashish

Transformer Energization Studies

Transformer energization studies are performed to demonstrate that the resonant overvoltages are well damped and that the magnitudes do not violate temporary overvoltage capability of station equipment. During transformer energization, two main phenomena occur: an inrush current and a voltage

Read More »
Transmission Line Energization Study
PSCAD
Chief Editor

Transmission Line Energization Study

In this article, Transmission Line Energization Study is demonstrated using Power Systems Computer Aided Design (PSCAD) software. This study illustrates the key points considered in a line energizing study. The PSCAD ‘Multiple-Run’ component is used to time the instant at

Read More »
Generator Excitation
Electrical Equipment
Chief Editor

Generator Excitation Control System

Introduction The basic function of a generator excitation control system is to provide a variable DC current to the synchronous generator field winding. By varying the DC voltage, and thereby the field current, the generator terminal voltage and reactive power

Read More »
impedance method
Electrical Equipment
Chief Editor

Impedance Method For Calculating Voltage Drop During Motor Start

This article covers all about the introduction to impedance method for calculating voltage drop during motor start, sample hand calculation and its comparison with ETAP software. Introduction To Impedance Method Impedance method for calculating voltage drop during motor start involves

Read More »
SELECTING THE RIGHT APPROACH FOR STARTING LARGE MOTORS
Electrical Equipment
Chief Editor

Selecting The Right Approach For Starting Large Motors

Selecting the right approach for starting large motors at the early stages of a project is very important. Hence, this selection will impact the integrity of the system, initial capital investment, operating costs and long-term reliability. This article helps in

Read More »

Author Information

Comments

Leave a Reply

Your email address will not be published. Required fields are marked *