Harmonic Analysis Methods

harmonic frequency scan

Harmonic analysis methods help engineers to calculate system harmonic levels resulting from harmonic sources on the system. This also requires a knowledge of the harmonic source characteristics and a representation of the system frequency response characteristics.

Below sections cover the aspects of harmonic levels and harmonic frequency response of harmonic analysis:

Harmonic Current Calculations

Most harmonic sources represent as ideal current sources for analysis purposes. That is, for analysis at each harmonic frequency, the nonlinear device represents a current source as indicated in below figure:

Modeling Nonlinear Loads by Current Sources
Modeling Nonlinear Loads by Current Sources

For most nonlinear devices, the representation is quite accurate up to harmonic voltage distortion levels of at least 10%.

The specific characteristics for different types of nonlinear devices fall into three general categories:

1) Power electronic type devices (converters, etc.)

2) Arcing type devices (arc furnaces, fluorescent lights)

3) Ferromagnetic devices (transformers)

For power electronic type devices, the harmonic generating characteristics can often be determined analytically. For arcing devices and transformers, it is usually necessary to use typical characteristics, unless better information is available.

System Frequency Response Calculations

Once the harmonic source characteristics are determined, the response of the system to these sources should be calculated. Important elements of the model used to perform these calculations include the following:

1) System short-circuit equivalent impedance
2) Capacitor banks
3) Characteristics of lines and cables on the system
4) Load characteristics

The system analysis can be performed using relatively simple hand calculations for some industrial circuits and simple distribution systems. However, most systems require some type of computer simulation program that can represent the system at multiple frequencies for analysis.

Simple Calculations

Simple Circuit for Hand Calculations
Simple Circuit for Hand Calculations

This circuit is adequate for analyzing many industrial circuits and some distribution circuits where capacitors are applied at the substation.

The most important calculation for this circuit is the resonant frequency as below:

Resonance Frequency
Resonance Frequency

If the calculated resonance is near one of the characteristic harmonics of the source, the potential for problems needs further evaluation.
The next step is to calculate the actual system impedance at the characteristic harmonics of the source:

system impedance

Once Zh is obtained at each characteristic harmonic, the voltage magnitude can be calculated at each harmonic as follows:

voltage magnitude

where, Ih = the source current at each characteristics harmonic

Relevant Contents

Related Posts

Electrical Equipment
Chief Editor

Selection of NGR (Neutral Grounding Resistor)

Selection of NGR mainly depends on key factors such as the voltage rating, the time rating and the let-through-current rating. Voltage Rating An NGR must be rated for system line-to-neutral voltage—the voltage across the resistor when a single-phase bolted ground

Read More »
protection coordination
ETAP
Chief Editor

Protection and Coordination Analysis

This article demonstrates the high level step by step procedure to perform the protection and coordination analysis in ETAP software. Below are the steps: Select protective devices models from editor Once the single line diagram and data entry is complete

Read More »
directional protection
Protection
Chief Editor

Directional Overcurrent Protection

Application Directional Overcurrent Protection is useful for all network components in which the direction of flow of power is likely to change, notably in the instance of a short circuit between phases or of an earthing fault (single phase fault).

Read More »
arc flash
Arc Flash
Chief Editor

Arc Flash Mitigation With Maintenance Mode

Introduction To Maintenance Mode The Arc Flash Mitigation with Maintenance Mode provides a method to reduce clearing time of arc flash energy. A circuit breaker equipped with Maintenance Mode can improve safety by providing a simple and reliable method to

Read More »
Tur-Gov
Electrical Equipment
Chief Editor

Generator Turbine Governor Control

Introduction The generator turbine governor control regulates rotational speed in response to changing load conditions. The governor output signal manipulates the position of a steam inlet valve or nozzles which in turn regulates the steam flow to the turbine. Turbine-generator

Read More »
Digsilent Power Flow Analysis
DIgSILENT
Chief Editor

DIgSILENT Load Flow Analysis

This article shows the step by step process on how to run DIgSILENT Load Flow Analysis. This will help engineers to practice on how to run load flow analysis on DIgSILENT Power Factory Software. Sample Network Model You can setup

Read More »

Author Information

Comments

Leave a Reply

Your email address will not be published. Required fields are marked *