Impedance Method For Calculating Voltage Drop During Motor Start

impedance method

This article covers all about the introduction to impedance method for calculating voltage drop during motor start, sample hand calculation and its comparison with ETAP software.

Introduction To Impedance Method

Impedance method for calculating voltage drop during motor start involves the reduction of the system to a simple voltage divider network. In this method, voltage at any point (bus) in a circuit is found by taking known voltage (source bus) times the ratio of impedance to the point in question over total circuit impedance.

Simplified Impedance Diagram
Simplified Impedance Diagram

For above circuit, using voltage divider theory, we can write the motor terminal bus voltage as below:

motor terminal voltage

or more generally,

motor terminal voltage

Above expression for V also analyze the effect of adding a large capacitor bank at the motor bus. The addition of negative vars causes X1 or Z1 to become larger in both numerator and denominator. Hence, the bus voltage V increases and approaches 1.0 per unit as the limiting improvement.

Locked-rotor impedance for three-phase motor is given by:

locked rotor impedance
LRA is the locked-rotor current at rated voltage

This value in per unit is equal to the inverse of the inrush multiplier on the motor rated kVA base:

locked rotor impedance
(LRA/FLA) = LRC in per unit

A starting motor is accurately represented as a constant impedance course. Hence, the impedance method is a very convenient and acceptable means of calculating system bus voltages during motor starting.

Validity of the impedance method can be seen and is usually used for working hand calculations. Where other than simple radial systems are involved, the digital computer greatly aids in obtaining necessary network reduction.

To obtain results with reasonable accuracy, however, various system impedance elements must be represented as complex quantities rather than as simple reactances.

Sample Calculation For Calculating Voltage Drop During Motor Start

Step-1: Enter Source / Grid and Motor Input Data

Step-2: Calculate Source Impedance at Source MVA and Convert to Common 100 MVA Base (Z2)

Step-3: Calculate Motor Impedance in Locked-Rotor Condition and Convert to Common 100 MVA Base (Z1)

motor starting voltage
Figure-(1)

Step-4: Calculate Motor Terminal Bus Voltage and Voltage Dip During Motor Start

Motor Terminal Bus Voltage (V) = E [ Z1 / ( Z1 + Z2 ) ] = 1 [ 3.43 / ( 3.43 + 0.35 ) ] = 0.9074 Per Unit OR 90.74%

Voltage Dip During Motor Start = 100 % – 90.74 % = 9.26 %

Simulation and Comparison With ETAP Software

Motor Input Data

motor name plate
motor impedance

ETAP Plot Result For Motor Starting Voltage Dip With 25 KA Source Fault Current

motor starting voltage etap
Figure -(2)

Conclusion

It can be concluded that the voltage (V) at motor terminal bus derived (Figure-(1)) using Impedance Method or Voltage Divider Method is 90.73 % which is closely matching with the value of 90.8 % as shown in Figure-(2).

Relevant Contents

Related Posts

Electrical Equipment
Chief Editor

Selection of NGR (Neutral Grounding Resistor)

Selection of NGR mainly depends on key factors such as the voltage rating, the time rating and the let-through-current rating. Voltage Rating An NGR must be rated for system line-to-neutral voltage—the voltage across the resistor when a single-phase bolted ground

Read More »
protection coordination
ETAP
Chief Editor

Protection and Coordination Analysis

This article demonstrates the high level step by step procedure to perform the protection and coordination analysis in ETAP software. Below are the steps: Select protective devices models from editor Once the single line diagram and data entry is complete

Read More »
directional protection
Protection
Chief Editor

Directional Overcurrent Protection

Application Directional Overcurrent Protection is useful for all network components in which the direction of flow of power is likely to change, notably in the instance of a short circuit between phases or of an earthing fault (single phase fault).

Read More »
arc flash
Arc Flash
Chief Editor

Arc Flash Mitigation With Maintenance Mode

Introduction To Maintenance Mode The Arc Flash Mitigation with Maintenance Mode provides a method to reduce clearing time of arc flash energy. A circuit breaker equipped with Maintenance Mode can improve safety by providing a simple and reliable method to

Read More »
Tur-Gov
Electrical Equipment
Chief Editor

Generator Turbine Governor Control

Introduction The generator turbine governor control regulates rotational speed in response to changing load conditions. The governor output signal manipulates the position of a steam inlet valve or nozzles which in turn regulates the steam flow to the turbine. Turbine-generator

Read More »
Digsilent Power Flow Analysis
DIgSILENT
Chief Editor

DIgSILENT Load Flow Analysis

This article shows the step by step process on how to run DIgSILENT Load Flow Analysis. This will help engineers to practice on how to run load flow analysis on DIgSILENT Power Factory Software. Sample Network Model You can setup

Read More »

Author Information

Comments

Leave a Reply

Your email address will not be published. Required fields are marked *