Phase Voltage Unbalance in Three-Phase System

balanced and unbalanced voltages

Causes of Phase Voltage Unbalance

Most utilities use four-wire grounded-wye distribution systems. This is to connect single-phase distribution transformers to phase-to-neutral to supply single-phase loads, such as residences and street lights.

Variations in single-phase loading cause the currents in the three-phase conductors to be different, producing different voltage drops. This causes the phase voltages to become unbalanced.

Normally the maximum phase-voltage unbalance will occur at the end of the primary distribution system. However, the actual amount will depend on how well the single-phase loads are balanced between the phases on the system.

Perfect balance can never be maintained because the loads are continually changing, causing the phase-voltage unbalance to vary continually.

Blown fuses on three-phase capacitor banks will also unbalance the load and cause phase-voltage unbalance.

Industrial plants make extensive use of 480Y/277 V utilization voltage to supply lighting loads connected phase-to-neutral. Proper balancing of single-phase loads among the three phases on both branch circuits and feeders is necessary to keep the load unbalance and the corresponding phase-voltage unbalance within reasonable limits.

How Phase Voltage Unbalanced Is Measured?

The simplest method of expressing the phase-voltage unbalance is to measure the voltages in each of the three phases.

The amount of voltage unbalance is better expressed in symmetrical components as the negative sequence component of the voltage:

No alt text provided for this image

Effect of Phase Voltage Unbalance

When unbalanced phase voltages are applied to three-phase motors, the phase voltage unbalance causes additional negative-sequence currents to circulate in the motor, increasing the heat losses primarily in the rotor.

The most severe condition occurs when one phase is opened and the motor runs on single-phase power.

Below shows the recommended derating for motors as a function of percent phase-voltage unbalance:

No alt text provided for this image

Although there will generally be an increase in the motor load current when the phase voltages are unbalanced, the increase is insufficient to indicate the actual temperature rise that occurs because NEMA current-responsive thermal or magnetic overload devices only provide a trip characteristic that correlates with the motor thermal damage due to normal overload current (positive-sequence) and not negative-sequence current.

When a motor trips out, the first step in determining the cause is to check the running current after it has been restarted to make sure that the motor is not overloaded.

The next step is to measure the three-phase voltages to determine the amount of phase-voltage unbalance.

The above figure of Derating Factor Vs % Voltage Unbalance indicates that where the phase-voltage unbalance exceeds 2%, the motor is likely to become overheated if it is operating close to full load.

In general, single-phase loads should not be connected to three-phase circuits supplying equipment sensitive to phase-voltage unbalance. A separate circuit should be used to supply this equipment.

Related Posts

Electrical Equipment
Chief Editor

Selection of NGR (Neutral Grounding Resistor)

Selection of NGR mainly depends on key factors such as the voltage rating, the time rating and the let-through-current rating. Voltage Rating An NGR must be rated for system line-to-neutral voltage—the voltage across the resistor when a single-phase bolted ground

Read More »
protection coordination
ETAP
Chief Editor

Protection and Coordination Analysis

This article demonstrates the high level step by step procedure to perform the protection and coordination analysis in ETAP software. Below are the steps: Select protective devices models from editor Once the single line diagram and data entry is complete

Read More »
PV inverter
General
Chief Editor

Inverter Controls in AC Microgrids

Inverter controls in AC microgrid allows delivering distributed power and providing grid support services during regular operation of the grid. It also allows the powering isolated islands in case of faults/contingencies to increase the performance and reliability of electrical system.

Read More »
short circuit
General
Chief Editor

X/R Ratio in Low-Voltage Short Circuit Studies

This article discusses about the importance of X/R ratio in low voltage short circuit studies. Introduction In some short circuit studies, the X/R ratio is ignored when comparing the short circuit rating of the equipment to the available fault current

Read More »
harmonic frequency scan
General
Chief Editor

Harmonic Analysis Methods

Harmonic analysis methods help engineers to calculate system harmonic levels resulting from harmonic sources on the system. This also requires a knowledge of the harmonic source characteristics and a representation of the system frequency response characteristics. Below sections cover the

Read More »
impedance method
Electrical Equipment
Chief Editor

Impedance Method For Calculating Voltage Drop During Motor Start

This article covers all about the introduction to impedance method for calculating voltage drop during motor start, sample hand calculation and its comparison with ETAP software. Introduction To Impedance Method Impedance method for calculating voltage drop during motor start involves

Read More »

Author Information

Comments

Leave a Reply

Your email address will not be published. Required fields are marked *