Switching of Capacitive Circuit

Capacitor Bank Switching

Introduction

Shunt capacitors, connected between line and neutral or line and ground, are common sights on power systems. They may be there to correct a lagging power factor or in cases, to provide voltage support for the system.

The transient current that occurs when the capacitor bank is energized can be significantly higher than its rated current. In this case, the frequency of the transient can reach a few kilohertz.

The frequency, peak, and rate of change (i.e. di/dt) of the current must be controlled in order to ensure that the circuit breaker can withstand the capacitor energizing currents, without sustaining damage.

In some applications they are switched in and out quite frequently as the system load varies and the system voltage fluctuates. It will be shown that such switching operations are nontrivial and should be carefully considered when designing capacitor banks and their associated switching equipment.

Purpose

The purpose of this study is to illustrate key points that need to be considered when the capacitor bank is energized. In general, energizing a capacitor gives rise to fast transients.

When capacitor is closed on to a source voltage with inductive source internal reactance as shown in the model below, the current drawn by the capacitor will be directly dependent on the instantaneous voltage at which it was closed. If CB/switch is closed at voltage zero crossing, the capacitor current will smoothly rise from zero.

When CB is closed at peak of voltage, the inrush current will be high. This high capacitive current through the source inductive internal reactance can result in high transient switching over voltages. (High capacitive leading current across source inductance will cause voltage rise across capacitance).

Modelling Capacitive Circuit in PSCAD

PSCAD Model of a Capacitive Circuit
PSCAD Model of a Capacitive Circuit

Results of Capacitive Circuit Energization

Result of capacitive circuit energizing at zero instant of system voltage:

Energizing at zero instant of system voltage
Energizing at zero instant of system voltage

Result of capacitive circuit energizing at peak instant of system voltage:

Energizing at peak instant of system voltage
Energizing at peak instant of system voltage

Conclusion

The above analysis concludes that point of switching on the voltage wave plays an important role in generation of transient over voltages and over currents.

Switching ON the capacitor at peak of voltage wave causes high capacitive inrush current and highest over voltages. On the other hand, switching ON the capacitor at zero point of voltage wave causes lowest inrush current & lowest over voltages.

Relevant Contents

Related Posts

Transformer Inrush
PSCAD
Ashish

Transformer Energization Studies

Transformer energization studies are performed to demonstrate that the resonant overvoltages are well damped and that the magnitudes do not violate temporary overvoltage capability of station equipment. During transformer energization, two main phenomena occur: an inrush current and a voltage

Read More »
Transmission Line Energization Study
PSCAD
Chief Editor

Transmission Line Energization Study

In this article, Transmission Line Energization Study is demonstrated using Power Systems Computer Aided Design (PSCAD) software. This study illustrates the key points considered in a line energizing study. The PSCAD ‘Multiple-Run’ component is used to time the instant at

Read More »
Switching an Inductive circuit
Power System Analysis
Ashish

Switching Of An Inductive Circuit

Introduction Switching of an inductive circuit deserves special attention because this operation may lead to high-voltage transients. These transients can damage the involved equipment. Inductive loads are those components capable of generating a magnetic field and typically consist of solenoids,

Read More »
switching transient
General
Ashish

Introduction to Power System Switching Transients

Introduction Power system switching transients occur each time, an abrupt circuit change occurs. This circuit change is usually the result of a normal switching operation, such as breaker opening or closing or simply turning a light switch on or off.

Read More »

Author Information

Comments

Leave a Reply

Your email address will not be published. Required fields are marked *