Transient Recovery Voltage (TRV) and Rate of Rise of Recovery Voltage (RRRV)

TRV

Introduction

Transient Recovery Voltage (TRV)

As per IEEE C37.011, “TRV is the voltage difference between the breaker terminals immediately after the current interruption of the breaker”.

It is simply the difference in the power system response voltages on the source side and on the load side of the circuit breaker.

Transient Recovery Voltage (TRV)

Rate of Rise of Recovery Voltage (RRRV)

RRRV: Peak transient recovery voltage divided by the total time from zero voltage to peak voltage. Level of TRV and the RRRV are key factors in determining whether the fault can be cleared successfully.

The voltage across the breaker may be considered in two successive time intervals: one during which transient recovery voltage (TRV) exists where high frequency oscillations are observed, followed by second during which recovery voltage exists where power-frequency oscillations are observed (transient has decayed).

Transient Recovery Voltage (TRV) and Rate of Rise of Recovery Voltage (RRRV)
TRV and RRRV

Purpose of TRV Study

The purpose of TRV study is to verify that the transient voltage experienced by the breaker during current interruption is within the capability of the breaker under worst-case scenarios.

The nature of TRV depends on nature of the interrupted circuit.

  • LRC circuit behavior
  • Travelling waves in lines

Modelling Requirements

System modelling plays an important role in carrying out the TRV and RRRV studies. As the TRV is a ‘fast event’ (10s of kHz), the system must be modelled for frequencies ranging from the fundamental to few kilohertz (kHz). For the most part, and especially for conductors requires frequency-dependent modelling.

TRV is mainly due to an oscillatory transient. L and C components of the circuit determines the frequency and magnitude of the transient. Circuit components of the station has a major impact of TRV (bushing capacitances of equipment). So, it is important to represent station equipment layout/capacitances for TRV studies.

First Pole To Clear

The three poles (of breaker) do not break the current at the same instant due to 120-degree phase shift on the 3 phases.

  • First pole to clear typically has the worst TRV
  • Grounding conditions have an impact (grounded/ungrounded)

Standards Covering TRV Analysis

  • IEEE C37.011-2011: IEEE Guide for the Application of Transient Recovery Voltage for AC High-Voltage Circuit Breaker
  • IEEE C37.06-2009: IEEE Standard for AC High-Voltage Circuit Breakers Rated on a Symmetrical Current Basis – Preferred Ratings and Related Required Capabilities for Voltages Above 1000.
  • IEC 62271-100: High-Voltage switchgear and control gear – Part 100: Alternating-current circuit-breaker. Edition 2.0, 2008-04

TRV Study Example

Below is the example illustrating the TRV studies. From the below graph, the TRV for breaker is exceeding the withstand capability of circuit breaker’s capability provided by the vendor in the form of family of curves. If specific capability curves are not available from vendor, IEC 62271-100 provides the required information.

Relevant Contents

Related Posts

protection coordination
ETAP
Chief Editor

Protection and Coordination Analysis

This article demonstrates the high level step by step procedure to perform the protection and coordination analysis in ETAP software. Below are the steps: Select protective devices models from editor Once the single line diagram and data entry is complete

Read More »
Digsilent Power Flow Analysis
DIgSILENT
Chief Editor

DIgSILENT Load Flow Analysis

This article shows the step by step process on how to run DIgSILENT Load Flow Analysis. This will help engineers to practice on how to run load flow analysis on DIgSILENT Power Factory Software. Sample Network Model You can setup

Read More »
Transformer Inrush
PSCAD
Ashish

Transformer Energization Studies

Transformer energization studies are performed to demonstrate that the resonant overvoltages are well damped and that the magnitudes do not violate temporary overvoltage capability of station equipment. During transformer energization, two main phenomena occur: an inrush current and a voltage

Read More »
Capacitor Bank Switching
PSCAD
Chief Editor

Switching of Capacitive Circuit

Introduction Shunt capacitors, connected between line and neutral or line and ground, are common sights on power systems. They may be there to correct a lagging power factor or in cases, to provide voltage support for the system. The transient

Read More »
Transmission Line Energization Study
PSCAD
Chief Editor

Transmission Line Energization Study

In this article, Transmission Line Energization Study is demonstrated using Power Systems Computer Aided Design (PSCAD) software. This study illustrates the key points considered in a line energizing study. The PSCAD ‘Multiple-Run’ component is used to time the instant at

Read More »
Switching an Inductive circuit
Power System Analysis
Ashish

Switching Of An Inductive Circuit

Introduction Switching of an inductive circuit deserves special attention because this operation may lead to high-voltage transients. These transients can damage the involved equipment. Inductive loads are those components capable of generating a magnetic field and typically consist of solenoids,

Read More »

Author Information

Comments

One Response

  1. Transient recovery voltage and transient restriking voltage and active recovery voltage. This three terms are same or different. Pls tell me sir and if you have formula for this then provide me.

Leave a Reply

Your email address will not be published. Required fields are marked *